AC vs DC switch ratings: why a 16 A AC switch is not a 16 A DC switch

2026-11-28来源 dev.toEnglish

A 16 A 250 V AC rocker is not a 16 A switch on DC. The reason is the arc: on AC it dies at the zero crossing, on DC it does not.

On AC the current passes through zero 100 or 120 times a second, so an arc drawn at the contacts collapses within milliseconds. On DC there is no zero crossing: the arc burns until the gap exceeds the supply voltage, so contact erosion per operation is far higher.

Practical derating: a part quoted 16 A at 250 V AC is often 10 A at 30 V DC and much less at 110 V DC, if it carries a DC rating at all. No DC rating on the drawing means the AC number says nothing about DC duty.

Where it bites: 12 / 24 / 48 V battery and solar circuits reusing a mains rocker that fits the cutout; DC motor reversing; 24 V DC coils adding back-EMF. Fix with a DC-rated switch with magnetic blowout, a contactor, or a snubber sized for the load.

Check the utilisation category and the voltage it applies to. DC-13 at 24 V is not DC-13 at 110 V.

Field notes from a manufacturer, not an independent test report. More on the AC vs DC ratings page, derating on the 16(4)A page, index at answers.